KTU7 Molded Case Circuit Breaker Busbar Alternatives
Question:
Why would you use compact bus bar on a KTU7 molded case circuit breaker? What are the alternatives?
Answer:
The most common application of KTU7 that requires compact busbar would be in a multiple motor starter control panel used with KTA7. The KTA7 would be used to protect motor loads while KTU7 would be used to protect non-motor loads (transformer or heater). In mixed applications, KT7-32-DB-__ compact busbar will not work with KTU7, but KTU7-D-DB-__ works well with both KTA7 and KTU7. If availability of KTU7 compact busbar becomes an issue then you may want to consider one of the following alternatives.
|
For additional information please contact your nearest authorized distributor, sales representative, or call our customer service or technical support lines.