The PF softstarters between 5 and 480 Amps are fitted with 2 sets of connection lugs on the load side (at the bottom of the unit). This is for the purpose of delta wiring a motor. See page 3-4, fig.3.5, of PF Softstarter User manual.Where a motor needs to be star wired (as in fig 3.4, same page of above publication), the motor cables should be connected to terminals 2/T1, 4/T2 and 6/T3. If a star wired motor is connected to terminals 8/T4, 10/T5 and 12/T6, the motor will run continually as soon as power is applied to L1, L2 and L3. Hence it will appear that the bypass contactor is short circuit. (ROK48493)